ASHRAE 90.1

ASHRAE 90.1 energy monitoring, met and kept running

ASHRAE 90.1 is the US energy standard for buildings other than low-rise residential, adopted through state codes. Its section 8.4.3 requires new buildings of 25,000 sq ft or more to meter energy by end use and keep the data. Aqueduct is that metering and record.

Powered by aQ Assure and aQ EnergySmart
Condenser fans seen from above
Site performance · this quarter
-8.4% vs expected
Weather normalizedBelow baseline
Demo data
Peak demand today
612 kW
Contracted 650 kWChillers sequenced
Demo data

Who it applies to

The standard covers commercial buildings, multifamily buildings over three stories and hotels of any height. It reaches owners through state energy codes: under federal law each state must certify that its commercial code meets the edition the Department of Energy has affirmed, currently 90.1-2022.

Chapters set requirements for the envelope (5), HVAC (6), service water heating (7), power (8) and lighting (9). Most are design rules checked at permit. Section 8.4.3 is different: it requires metering that has to keep working after handover.

Section 8.4.3

What electrical energy monitoring requires

Clause numbers follow 90.1-2022 as amended by Addendum br (2025). Your code official decides compliance.

RequirementWhat it asks forData Aqueduct supplies
8.4.3.1, monitoringSeparate measurement of total electricity, HVAC, interior lighting, exterior lighting, receptacles and refrigeration.Sub-meters or CT clamps per category, mapped to panels in aQ Core.
8.4.3.1, tenantsIn tenant buildings, the same categories measured per tenant.Meters assigned to each tenancy, with its own dashboard and export.
8.4.3.2, recordingData recorded at least every 15 minutes.Interval readings stored at 15 minutes or finer.
8.4.3.2, reportingReports at least hourly, daily, monthly and annually, shared with each tenant.Hourly to annual reports per category and tenant.
8.4.3.2, retentionAll data kept for at least 36 months.Full interval history retained and exportable.
By the numbers

Numbers that matter

9.8%

Site energy savings DOE found for 90.1-2022 over the 2019 edition.

Source: DOE determination, Federal Register 2024
6 Mar 2026

Deadline for states to certify codes against 90.1-2022.

Source: DOE determination, Federal Register 2024
2025

The 2025 edition is published, adding graphical display of energy data where direct digital controls exist. A DOE determination is pending.

Source: ASHRAE
Standards and regulations

Related standards

ASHRAE 62.1 LEEDBuilding performance standardsENERGY STAR Portfolio Manager
Trusted at scale
Read the case studies
Deployed275+

sites in 21 countries run on Aqueduct.

Healthcare22 hospitals

and 9 clinics in one of India’s top hospital chains.

AirportsA top 25

US airport running water intelligence on Aqueduct.

Real estate20M+ sq ft

of commercial real estate under Aqueduct.

Manufacturing300 acres

FMCG manufacturing campus.

Food and dairyMajor dairy

operations run on Aqueduct.

Questions

Common questions

Buildings under 25,000 sq ft, tenant spaces under 10,000 sq ft, dwelling units and hospital critical and life-safety branches. A category under a tenth of the building load may be combined with another, and Aqueduct can still meter exempt spaces where the owner wants the data.

Mainly through alterations and additions, which must meet the code in force for the work being done. Ongoing operation is not policed by the standard itself, which is why metering often stops being read after handover.

The one your state or city has adopted, which may lag the latest ASHRAE edition by several years. Local amendments can also change the metering section, so confirm the edition and any amendments with the authority having jurisdiction before metering is designed.

At least 36 months under section 8.4.3.2. Aqueduct keeps the full interval history beyond that minimum, so a tenant question or an audit three years on can still be answered from the original readings rather than from summary reports. See load disaggregation.