WELL Building Standard

WELL v2 air features, met with continuous sensor data

The WELL Building Standard, from IWBI, certifies buildings on health and wellbeing. Its Air concept sets limits for particulates, gases and CO2, and accepts continuous sensor data as evidence for several features. Aqueduct supplies those readings per zone through aQ AirSafe.

Powered by aQ Assure and aQ AirSafe
Ceiling air unit under a glass roof
Hall B · occupied
1,184 ppm CO₂
Ventilation adjusted
Demo data
Site air health · 24h
Unhealthy, driven by CO₂
Over 2000 ppm for 20+ minutes within an occupied hour. Increase ventilation, raise outdoor air supply or check the AHU economizer.
3 of 4 zones breaching · outdoor 67°F
Demo data

Who it applies to

Owners and tenants pursuing WELL v2 certification or the WELL Performance Rating. The current version is WELL v2, Q2 2025. The Air concept has four preconditions, A01 to A04, which every project must meet, and optimizations A05 to A14 that earn points.

A01 requires air parameters to be measured at least once a year and the results submitted annually, so the evidence does not end at certification.

WELL v2 Air

Features that need measured data

Feature codes and thresholds from WELL v2, Q2 2025. IWBI and its performance testing agents decide certification.

RequirementWhat it asks forData Aqueduct supplies
A01 Air Quality (precondition)PM2.5 at most 15 µg/m3, PM10 50, TVOC 500 µg/m3 by sensor, CO 9 ppm, ozone 51 ppb; by performance test or sensor data.Continuous PM2.5, PM10, TVOC, CO and ozone per zone.
A03 Ventilation Design (precondition)Design to ASHRAE 62.1, or monitoring that keeps CO2 at 900 ppm or 500 above outdoors.CO2 per zone against outdoor CO2.
A05 Enhanced Air QualityTighter limits, such as PM2.5 at 12 or 10 µg/m3 and NO2 at 21 ppb.The same sensors, judged against the stricter thresholds.
A06 Enhanced Ventilation DesignDCV holding CO2 under 900 or 750 ppm in nearly all regularly occupied spaces.CO2 compliance per space, as a share of occupied hours.
A08 Air Quality Monitoring and AwarenessMonitors for at least three parameters, calibrated every three years, with occupant displays updated every 15 minutes.Sensor register with calibration dates and live data for displays.
By the numbers

Thresholds

750 ppm

The stricter A06 CO2 tier, or 350 ppm above outdoor air.

Source: WELL v2 A06
25 µg/m3

A01 PM2.5 limit where outdoor PM2.5 is at or above 35 µg/m3.

Source: WELL v2 A01
Standards and regulations

Related standards

ASHRAE 62.1 LEEDDubai Al Sa'fatASHRAE 170
Trusted at scale
Read the case studies
Deployed275+

sites in 21 countries run on Aqueduct.

Healthcare22 hospitals

and 9 clinics in one of India’s top hospital chains.

AirportsA top 25

US airport running water intelligence on Aqueduct.

Real estate20M+ sq ft

of commercial real estate under Aqueduct.

Manufacturing300 acres

FMCG manufacturing campus.

Food and dairyMajor dairy

operations run on Aqueduct.

Questions

Common questions

For A01 Air Quality, yes: the feature accepts either a performance test or continuous sensor data. Sensors must meet IWBI specifications for accuracy and placement, and your WELL AP confirms which route the project uses. aQ AirSafe sensors can supply that data per zone.

One display per 500 m2 (5,400 sq ft) of regularly occupied space, mounted between 1.1 and 1.7 m. Aqueduct keeps the register of those monitors with their calibration dates, so the evidence for A08 is ready at recertification.

Ongoing data. A01 asks for air parameters to be measured at least yearly and submitted, so a continuous sensor record avoids a separate annual test campaign. Aqueduct exports the year of readings per zone for submission to IWBI.

Yes, through its ventilation features. A03 can be met by monitoring that holds CO2 at 900 ppm, or 500 ppm above outdoor air, and A06 earns points for lower levels across occupied spaces. aQ AirSafe reports how many occupied hours each space stayed under its level. See CO2 monitoring.